What are the installation requirements of indoor air sampling pipe?

2020-04-07 14:01:29

1. When sampling under the ceiling, the pipe is suspended under the ceiling of the monitoring area, which can be directly attached to the ceiling, or it can be about 100mm away from the ceiling, and one to four pipes can be arranged to monitor the whole area.

2. The distance between sampling points shall not exceed 9 meters (30 feet). Similarly, the distance between adjacent pipes should not exceed 9 meters, and it is better to be closer.

3. The sampling point shall be at least 25 mm (1 inch) but not more than 100 mm (4 inches) away from the ceiling, with the sampling point facing the room. In this way, the sampling point is located at the lower edge of the warm air, which often causes smoke stratification when the environment is heated and the actual fire situation.


吸气式感烟探测器


4. The sampling pipeline shall be fixed every 1.5m.

5. The sampling hole shall be clearly marked

The inspiratory smoke fire detector independently developed by wittan intelligent technology realizes the centralized monitoring and management of the inspiratory smoke fire detector. These products are used in the fire control system to provide high-quality security for urban management and residents' life. The integrated management solution uses advanced technologies such as big data, Internet of things and cloud computing to alarm the electrical fire alarm, toxic gas leakage alarm and point type smoke fire detector, so as to realize the unified monitoring of the platform, and effectively discover the potential safety hazards before the fire; after the fire, timely inform the personnel to evacuate, and reasonably and effectively solve the situation of inadequate supervision.


Label

Recent browsing:

contact us

Serve you 24 hours, solve your needs and share your doubts

137.jpg

TEL:021-51090861   

E-MAIL:office@v-tecfire.com   

FAX:021-37560538   

ZIP CODE:210040

ADD:Third floor, building 2, No. 6400, Hangnan Road, Fengxian District, Shanghai China

Recruitment Agents

To eliminate fire and build social security with innovative technology

Name:
Contact:
Content:
checkcode:
Copyright © Shanghai V-TEC Intelligent Technology Co., Ltd All rights reserved Record No:沪ICP备19040963号 Specializing inInspiratory smoke fire detector,point type smoke fire detector,smoke detector,Welcome to inquire! Service support:火箭头网络